Fire Extinguisher 6-Year & Hydrostatic Test Date Calculator

Find exact 6-year internal maintenance and 5- or 12-year hydrostatic test due years for ABC, CO2, Class K, clean agent, foam, and disposable extinguishers.

NFPA 10 · OSHA 1910.157

Fire Extinguisher 6-Year & Hydrostatic Test Calculator

Enter the manufacture year stamped on the cylinder (and any prior service years) to find the next 6-year internal exam and hydrostatic test due dates.

Stamped on the cylinder bottom or shoulder.

6-Year Internal Examination

2026

Due this year

12-Year Hydrostatic Test

2032

Due in 6 years

Rule note (NFPA 10 Table 7.3.3.1 & Table 8.3.1): Requires monthly visual check, annual certified maintenance, 6-year internal teardown, and 12-year hydrostatic test.

Tracking dozens or hundreds of units?

GreenTagWorks schedules these intervals automatically, alerts you before items go overdue, and keeps audit-ready QR logs.

Get notified at launch

General information only, not legal or engineering advice. Always verify against the equipment label, manufacturer manual, and local AHJ rules. Official reference: OSHA 29 CFR 1910.157 (Portable Fire Extinguishers).

Plain-Language Compliance Guide

OSHA Fire Extinguisher Inspection Requirements

Monthly visual checks, annual maintenance, 6-year internal exams, hydro intervals, and the records OSHA and NFPA 10 expect.

Read the guide

Frequently Asked Questions

Does a 12-year hydrostatic test reset the 6-year internal examination clock?

Yes. Under NFPA 10, a hydrostatic test includes a complete teardown and internal examination of the extinguisher, which resets the 6-year internal exam interval starting from the year of the hydrostatic test.

Where do I find the manufacture year on a fire extinguisher?

Look for a 2-digit or 4-digit year stamped directly into the metal cylinder—usually on the bottom ring, collar, or shoulder. Do not rely solely on the paper inspection tag, as tags can be replaced during annual maintenance.

Do CO2 and Class K fire extinguishers need a 6-year internal examination?

No. Carbon dioxide (CO2), wet chemical (Class K), and stainless steel water extinguishers follow a 5-year hydrostatic test cycle. Because they are opened and inspected every 5 years during hydrotesting, there is no separate 6-year internal exam.

Can a disposable (non-rechargeable) fire extinguisher be hydrotested?

No. Under NFPA 10, non-rechargeable dry chemical extinguishers cannot be recharged or hydrostatically tested and must be removed from service 12 years from the date of manufacture.