Fire extinguisher inspection requirements
Monthly checks, annual maintenance, 6-year internal exams and hydrostatic tests, and the records to keep.
- OSHA 1910.157
- NFPA 10
Checked against the sources on . General information, not legal advice.
Monthly
Visual inspection
- Who
- A trained employee; no certification needed
- Record
- Month, year and inspector, on a tag, checklist or electronic record
Yearly
Maintenance
- Who
- A certified technician, usually a fire protection vendor
- Record
- Service tag on the unit; keep the record at least a year
Every 6 years
Internal examination (stored-pressure dry chemical)
- Who
- A certified technician
- Record
- Verification-of-service collar on the cylinder neck
Every 5 or 12 years
Hydrostatic test, by extinguisher type
- Who
- A certified technician with test equipment
- Record
- Test label or stamp; keep the certification until the next test
On this page
If your facility provides portable fire extinguishers for employees to use, OSHA's 29 CFR 1910.157 requires you to inspect, maintain and test them on a fixed schedule. Most local fire codes also adopt NFPA 10, the Standard for Portable Fire Extinguishers, which fills in how those checks are done and recorded.
Monthly visual inspection
Under 1910.157(e)(2), every portable extinguisher must be visually inspected at least once a month. NFPA 10 also asks for an inspection when a unit is first placed in service, and more often where units are exposed to corrosion, impact or tampering.
This is a quick walk-around that your own team can do. NFPA 10 does not require the monthly inspector to be certified.
What to check each month
- Location and access: in its assigned place, visible or marked with a sign, and not blocked.
- Instructions: the operating instructions on the nameplate are readable and face outward.
- Pressure gauge: the needle is in the green (operable) range. On non-rechargeable units with a push-to-test indicator, test it.
- Fullness: lift (heft) or weigh the unit to confirm it is full.
- Pin and tamper seal: the pull pin is in place and the tamper seal is unbroken.
- Condition: no obvious dents, corrosion, leaks or clogged nozzles. On wheeled units, check the tires, wheels, carriage, hose and nozzle too.
- Pressure gaugeNeedle in the green. Monthly.
- Pull pin and tamper sealPin in place, seal unbroken. Monthly.
- Hose and nozzleNot cracked, clogged or loose. Monthly.
- NameplateOperating instructions readable and facing out. Monthly.
- CylinderNo dents, corrosion or leaks. Lift it to check it is full. Monthly.
- Service tagMonth and year of the last annual maintenance, and who did it. Yearly, by a certified technician.
- Verification-of-service collarFitted at the 6-year internal examination. It only goes on with the valve off.
Recharge
Undercharged. Take it out of service.
Operable
In the green. Good.
Overcharged
Take it out of service.
Remove from service if
- The tamper seal is broken or the pull pin is missing.
- The gauge reads overcharged or undercharged.
- There is visible corrosion, a deep dent, or a damaged or clogged hose.
- There are signs of partial discharge, or the label cannot be read.
Annual maintenance
Under 1910.157(e)(3), every portable extinguisher must have a maintenance check once a year. This is more than the monthly look: it is a check of the mechanical parts, the extinguishing agent, the expelling means and the physical condition.
- Who does it: NFPA 10 requires a certified person, someone who has passed an exam acceptable to your authority having jurisdiction (AHJ) and has the tools, listed parts and the manufacturer's service manual. Most companies use a licensed fire protection vendor.
- No internal exam for stored-pressure units: OSHA notes that stored-pressure extinguishers do not need an internal examination as part of the annual check.
- Tagging: NFPA 10 requires a tag or label securely attached to the unit showing the month and year of maintenance, the person who did it and the service company.
Six-year internal examination
Under 1910.157(e)(4), stored-pressure dry chemical extinguishers that need a 12-year hydrostatic test, such as most ABC units, must be emptied and given a full maintenance examination every 6 years.
- What happens: a certified technician discharges the unit, inspects the inside of the cylinder and the valve, replaces worn parts from the manufacturer's manual, and recharges it.
- Verification-of-service collar: NFPA 10 requires a collar around the cylinder neck after any internal examination. It can only be fitted with the valve removed, which shows the unit was opened. It carries the month, year and service company.
- The clock restarts: if the unit is recharged or hydrostatically tested earlier, the 6 years count from that date.
- Disposable units: non-rechargeable dry chemical extinguishers have no 6-year examination. NFPA 10 has them removed from service 12 years after the date of manufacture.
Monthly visual inspection
Annual maintenance
6-year internal examination
12-year hydrostatic test
Years since manufacture
Hydrostatic testing
Under 1910.157(f), extinguisher shells are pressure-tested with water, never air or gas, to show they can hold pressure safely. The test is done by trained technicians with proper hydrostatic test equipment.
The interval depends on the extinguisher type (OSHA Table L-1):
| Extinguisher type | Test interval |
|---|---|
| Carbon dioxide (CO₂) | 5 years |
| Stored-pressure water, antifreeze | 5 years |
| Foam, AFFF, wetting agent | 5 years |
| Dry chemical, stainless steel shell | 5 years |
| Dry chemical, stored-pressure, mild steel, brazed brass or aluminum shell | 12 years |
| Dry chemical or dry powder, cartridge-operated, mild steel shell | 12 years |
| Halon 1211, Halon 1301 | 12 years |
- Hoses: hoses with a shut-off nozzle are tested on the same schedule as their extinguisher, at 1,250 psi for CO₂ hoses and 300 psi for dry chemical and dry powder hoses.
- Test early, or retire: test a unit before its interval, or take it out of service, if it shows corrosion or mechanical damage, or has been in a fire. A shell repaired by welding, soldering, brazing or patching must not be returned to service.
Records and audits
When an OSHA inspector or fire marshal walks through, a missing record looks the same as a missed inspection.
- Monthly inspections: NFPA 10 lets you record them on a tag on the unit, on a checklist kept on file, or electronically, as long as each entry shows the month, the year and who did it.
- Annual maintenance: OSHA requires a record of the maintenance date, kept for one year after the last entry or for the life of the shell, whichever is less, and available to OSHA on request.
- Hydrostatic tests: OSHA requires the test certification to be kept until the unit is tested again or taken out of service, whichever comes first. For low-pressure cylinders, NFPA 10 also requires a label on the shell with the tester's name, the test date and the test pressure.
GreenTagWorks
Track every extinguisher without chasing paper tags
Each extinguisher gets its own record and its own schedule: monthly for your team, yearly, 6-year and hydrostatic dates for the vendor. Inspectors walk a round building by building, scan each unit's barcode, QR or NFC tag, and mark it passed or failed with a reason and a photo. A failed unit goes out of service until someone fixes it, and every inspection is signed, timed and ready to hand to an auditor.
Official sources
- OSHA 29 CFR 1910.157, Portable fire extinguishers
- NFPA: Guide to fire extinguisher inspection, testing and maintenance
- OSHA interpretation: computerized bar code systems for extinguisher records (1996)
This guide summarizes publicly available requirements for general information. It is not legal advice. Standards change and local codes, state plans and manufacturers can ask for more, so check the official text, the manufacturer's instructions and your authority having jurisdiction, or ask a qualified safety professional, before relying on it.