OSHA 1910.137 · ASTM F496 / D120
Electrical Glove & Sleeve Retest Date Calculator
Calculate dielectric retest deadlines for Class 00 through Class 4 rubber insulating gloves and sleeves—and verify whether unissued stock is still within its 12-month shelf window.
Electrical Glove & Sleeve Retest Date Calculator
Calculate the exact dielectric retest deadline under OSHA 1910.137 Table I-5 and check whether unissued stock is still within its 12-month pre-issue window.
Tracking dozens or hundreds of units?
GreenTagWorks schedules these intervals automatically, alerts you before items go overdue, and keeps audit-ready QR logs.
General information only, not legal or engineering advice. Always verify against the equipment label, manufacturer manual, and local AHJ rules. Official reference: OSHA 29 CFR 1910.137 Table I-5 (Electrical Protective Equipment).
Plain-Language Compliance Guide
Electrical PPE Inspection Requirements (Gloves & Hot Sticks)
OSHA 1910.137 and ASTM D120 dielectric testing intervals, voltage classes, daily air tests, and documentation rules.
Frequently Asked Questions
When does the 6-month electrical glove retest clock start?
On the date the gloves are issued, but it never runs past 12 months from their last dielectric test. In its August 19, 2020 interpretation, OSHA agreed that gloves tested January 1 and issued October 1 must come out of service by January 1: the retest is due 6 months after issue or 12 months after the test, whichever comes first.
When are rubber insulating gloves considered issued?
When they are taken out of the manufacturer's original packaging. In the same August 2020 interpretation, OSHA said gloves that are unpacked, electrically tested and put back into storage count as issued, so the 6-month retest cycle applies to them.
How long can newly tested rubber insulating gloves sit on the shelf before being issued?
Up to 12 months from the last dielectric test date, while they stay in the manufacturer's packaging. If they remain unissued for more than 12 months, they must be electrically retested before they can be placed into service.
What is the retest interval for rubber insulating sleeves compared to gloves?
Rubber insulating gloves must be retested every 6 months once in service (and within 12 months of their last test). Rubber insulating sleeves and blankets have a 12-month in-service retest interval under OSHA 1910.137 Table I-5.
If gloves pass dielectric testing, do workers still need to inspect them daily?
Yes. OSHA 1910.137(c)(2)(ii) requires a visual inspection and air-inflation test before each day’s use and immediately following any incident that could reasonably have caused damage.