Emergency eyewash and safety shower inspection requirements
Weekly activation, the annual inspection, and the flow, temperature and placement numbers to check.
- OSHA 1910.151(c)
- ANSI/ISEA Z358.1
Checked against the sources on . General information, not legal advice.
Weekly
Activation (plumbed units)
- Who
- A trained technician or facilities staff
- Record
- Date, unit and person; on a tag or electronically
Per manufacturer
Fluid check (self-contained units)
- Who
- A trained technician
- Record
- Fluid level, seal and expiry date
Yearly
Full inspection against ANSI/ISEA Z358.1
- Who
- Facilities or a safety contractor with test gauges
- Record
- Flow, temperature, placement and access, with the result
On this page
Wherever someone's eyes or body may be exposed to corrosive materials, such as acids, caustics or battery electrolyte, OSHA 1910.151(c) requires "suitable facilities for quick drenching or flushing of the eyes and body" in the work area. That one sentence is all OSHA's rule says. To decide what "suitable" means, OSHA points employers to ANSI/ISEA Z358.1, which sets the weekly activation, the yearly inspection and the performance numbers below.
OSHA 1910.151(c) and ANSI Z358.1
OSHA has not incorporated Z358.1 into 1910.151(c), so some managers treat it as optional. In practice it is the measure you will be held to:
- OSHA refers to it. OSHA's interpretation letters direct employers to ANSI Z358.1 as guidance for meeting 1910.151(c).
- Plumbing codes adopt it. The International Plumbing Code and the Uniform Plumbing Code both require emergency fixtures to meet Z358.1, wherever your jurisdiction has adopted those codes.
Weekly activation
Weekly activation is one of the most often missed tasks in labs, warehouses and plants, mostly because 52 checks a year per station is hard to keep up on a paper tag.
Plumbed units: activate weekly
Every plumbed eyewash, eye/face wash, shower and combination unit is activated at least once a week.
- Run it long enough. Weekly activation confirms the valve works and flushes out sediment and stagnant water in the supply line, which can grow bacteria such as Legionella and Acanthamoeba. A two-second bump does not clear the line; run it until the water runs clear.
- Combination units: activate both the shower and the eyewash.
Self-contained units: check the fluid
Gravity-fed units without a water supply are checked visually to see whether the flushing fluid needs changing or topping up. Follow the manufacturer's schedule for the check and for replacing the fluid; many say weekly.
What to check each week
- Clear path: no pallets, carts, bins, hoses or locked doors between the work area and the station.
- Sign and lighting: the sign is in place and the area is well lit.
- Dust covers: clean, in place, and come off with the water flow without a separate hand movement.
- Valve: opens fully in 1 second or less and stays open without being held.
- Flow: eyewash streams are even in height, and the water runs clear without rust or debris.
- Leaks and damage: no leaks, heavy corrosion or damage to pipes, bowl or valves.
Tag out and point people to the nearest working station if
- The water pressure is low, uneven or sputtering.
- The valve sticks, takes more than a second to open, or closes when let go.
- The water is above 100°F or below 60°F.
- A self-contained unit's fluid is low, cloudy or past its date.
- Dust covers are broken, spray heads are clogged, or the path is blocked.
Annual inspection
Once a year, every eyewash, eye/face wash, shower and combination unit is inspected for conformance with Z358.1. This is usually done by facilities maintenance or a safety contractor, with a flow bucket or meter, an eyewash test gauge and a thermometer.
Performance and placement
| Unit | Minimum flow, for 15 minutes | Height and placement |
|---|---|---|
| Safety shower | 20 gal/min (75.7 L/min) | Showerhead 82 to 96 in above the floor; spray at least 20 in across at 60 in high; center at least 16 in from any obstruction; valve no higher than 69 in |
| Eye/face wash | 3 gal/min (11.4 L/min) | Flushing fluid between 33 and 53 in above the floor; at least 6 in from the wall or nearest obstruction |
| Eyewash | 0.4 gal/min (1.5 L/min) | Flushing fluid between 33 and 53 in above the floor; at least 6 in from the wall or nearest obstruction |
| Combination unit | Shower and eyewash flows at the same time | Both must keep full flow when run together |
Three checks that matter most
- Tepid water for 15 minutes. Z358.1 calls for tepid water; its guidance puts that at 60 to 100°F (16 to 38°C). Check that mixing valves hold that range for the full 15 minutes. Hotter water can harm the eye and speed up chemical reactions; colder water makes people stop flushing too soon.
- Within 10 seconds. The station must be reachable in about 10 seconds, roughly 55 feet, on the same level and without obstructions. Check that new racking, equipment or walls have not lengthened the route.
- Plumbing. Check supply valves cannot be shut off by accident, and check backflow preventers, mixing valve fail-safes (cold water still flows if the hot fails), freeze protection and alarms.
Common mistakes
- Using squeeze bottles as the eyewash. Personal eyewash bottles and drench hoses are supplemental. They do not replace a station that delivers 15 minutes of flushing.
- Relying on a sink faucet. A faucet does not give two gentle streams, stay open on its own, or hold tepid water.
- Letting things pile up in the way. A cart or mop bucket parked in front of a station blocks the route someone needs in an emergency.
- Not showing people where it is. Z358.1 requires workers who may be exposed to be shown where the stations are and how to use them, including holding their eyes open and flushing for the full 15 minutes.
Records
Z358.1 does not prescribe a tag or form, but a weekly activation with no record is almost impossible to prove. For each weekly and annual check, record:
- The unit's ID, location and the area it serves
- The date and the inspector's full name
- Pass or fail, and on the annual inspection the measured flow and water temperature
- Any repair, who signed it off, and the retest before the unit went back in service
GreenTagWorks
Every station's weekly check, without the paper tag
Each eyewash and shower is its own record on a weekly schedule, with the yearly inspection alongside. Technicians walk the round, scan each station's tag, which can be a waterproof NFC tag, and record the result. The assigned technician gets a notification and an email for each check, and a failed station goes out of service at once. You can see every station's history, week by week, when someone asks.
Official sources
- OSHA 29 CFR 1910.151, Medical services and first aid
- OSHA interpretation: ANSI Z358.1 guidance for complying with 1910.151(c) (2002)
- ISEA: Emergency eyewash and shower equipment selection, installation and use guide (2024, PDF)
- ANSI blog: ANSI/ISEA Z358.1, emergency eyewash and shower equipment
This guide summarizes publicly available requirements for general information. It is not legal advice. Standards change and local codes, state plans and manufacturers can ask for more, so check the official text, the manufacturer's instructions and your authority having jurisdiction, or ask a qualified safety professional, before relying on it.